arXiv:2611.17691v1 Announce Type: new Abstract: The increasing penetration of renewable energy and the rapid growth of AI data centers are introducing significant challenges to power system frequency security. There is an urgent need to identify grid-compatible resources capable of providing fast frequency support. This paper proposes a frequency-security-aware real-time economic dispatch (RTED) model that enables data center (DC) uninterruptible power supply (UPS) systems to provide steady-state power balancing, inertia response, and primary frequency response (PFR) services. Specifically, tractable analytical frequency-security constraints are derived and incorporated into the RTED framework through second-order cone programming (SOCP) formulation. The proposed model jointly optimizes energy, reserve, and inertia to minimize system operation cost while preventing under-frequency load shedding (UFLS). Numerical validation on a modified IEEE 39-bus system demonstrates that the proposed RTED model with UPS flexibility can economically support system operation and significantly improve frequency security under active-power deficit disturbances.