arXiv:2611.18534v1 Announce Type: new Abstract: Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.