arXiv:2611.17889v1 Announce Type: new Abstract: In grid-following converters, the synchronization path can transmit voltage disturbances to the current loop under weak or unbalanced grid conditions. This paper develops a Frenet-frame controller that derives its axes from the integral curve of the measured voltage at the point of common coupling. The tangential current governs active power, while the normal and binormal currents govern the transverse components of non-active power. Feedforward terms derived from the output filter model compensate curvature and torsion coupling, yielding identical nominal current dynamics across the axes. The controller operates without a phase-locked loop or sequence extraction. A reduced transverse model accounts for the finite bandwidth of geometric rate reconstruction and predicts a reduction in low-frequency coupling from voltage disturbances to current. Controller hardware-in-the-loop tests using real-time simulation of a three-phase four-wire converter show the shortest settling time after an active power reference step and the smallest peak power deviations during balanced voltage disturbances among the tested controllers. Under single-phase voltage unbalance, the method reduces peak binormal current and maximum phase-current total harmonic distortion relative to both benchmarks. It also settles to the commanded power in a weak-grid connection test where the phase-locked loop benchmark exhibits sustained oscillations.