A 16 A rocker switch is not a 16 A switch into every load. Rating plate numbers assume steady-state current with a defined power factor. LED drivers, motors and tungsten lamps all draw a current spike the contact never sees on a test bench with a resistive load.

What the numbers on the side actually promise

16(4)A 250V~ means 16 A resistive and 4 A at a defined inductive or motor load, per the utilization category on the drawing. Nothing on the body tells you the inrush withstand. That is why two switches both marked 16 A behave completely differently on the same LED driver.

Typical inrush multipliers worth remembering:

  • LED driver (capacitive input): 30–100× rated current for under 1 ms, limited only by the NTC or the absence of one.
  • Tungsten / halogen: 10–15× for 10–30 ms, because the filament is cold.
  • Induction motor: 6–8× for 100–300 ms, the slowest and most thermally punishing case.
  • SMPS with no inrush limiting: the worst offender, and the usual cause of welded contacts.

Why welding happens at all

At the instant of closing, the contacts touch over a microscopic area before full contact force settles. If the current spike arrives in that window, the contact spot melts. On the next opening, the molten bridge stretches and freezes into a welded bridge. The switch then either fails closed or reads a few milliohms and cooks itself.

This is a make-current failure, not an overload failure. A thermal breaker will not help. A bigger switch will.

How to size it without a lab

  1. Measure it. A clamp meter with peak hold on the load leg, switch closed ten times, take the highest reading. Most cheap clamps miss sub-millisecond peaks — treat the number as a floor, not the truth.
  2. Apply the derating factor from the utilization category. If the drawing gives AC-15 only at 4 A, do not run 16 A of motor.
  3. If the measured peak exceeds roughly 10× the switch's make rating, move the switching duty off the panel switch entirely: use the rocker to drive a relay or contactor coil, and let the contactor take the inrush.
  4. For repeated cycling of a capacitive load, prefer a switch with a documented make-current rating, or add an NTC / pre-charge resistor.

The cheap test that catches it early

Run the switch through 50 on/off cycles at the real load, then measure contact resistance across the closed contacts. A healthy silver-alloy contact pair stays in the low milliohms. If it has climbed into the tens of milliohms, the contacts are already pitted and the next stage is welding. This is the same measurement described in the 30 mΩ contact resistance note.

Where the rating table lies

Panel switches are often quoted at 16(4)A and tested at 6 cycles per minute on a resistive load. A coffee machine or a treadmill hits the switch once per use but with a 40 A spike. The switch is not defective; it was never rated for that duty. The honest fix is either a properly rated part or a relay, and the part selection gets easier once you read the category instead of the headline amperage — the reasoning is in the 16(4)A derating note.

I work with a manufacturer of these parts, so treat this as field notes rather than an independent test report. All the rating questions in this series are indexed at the answers page.

Other notes in this series