arXiv:2611.17361v1 Announce Type: cross Abstract: This paper presents a low-cost, open-source, single-phase immersion cooling testbed for studying liquid cooling of data center hardware. A 500 W titanium heater, standing in for server load, is submerged in a glass tank of mineral oil, a dielectric fluid. The heated oil is circulated by a magnetic drive pump through an air-cooled radiator. An ESP32 microcontroller logs three DS18B20 temperature sensors (heater surface, bulk fluid and ambient) and switches the pump, fan and heater through a relay module. The complete system costs INR 35,318 (about USD 380), built entirely from components available in India. At quasi-steady state under the full 500 W load, the heater surface reached 118.3 {\deg}C while the bulk oil stayed at 29.3 {\deg}C, only 8.0 {\deg}C above ambient. Thermal-resistance analysis shows that the heater-to-oil interface, limited by natural convection, accounts for about 92% of the total resistance (178.0 vs 16.0 m{\deg}C/W). The external loop therefore has spare capacity. CAD files, firmware and data are openly available, so the setup can be reproduced and used to compare dielectric fluids, loads and flow arrangements.