Most spec arguments I get dragged into are not about the switch. They are about the four numbers stamped on its side. A label like KCD4 16(4)A 250V~ T85 contains four independent limits, and each one gets misread in a predictable direction. Here is how each is actually defined, and what happens when you assume the wrong thing.

1. 16(4)A is two ratings, not one

The outside number is the rated current for the standard resistive test circuit in IEC 61058-1. The number in brackets is the rated current for the inductive test circuit, run at a defined lagging power factor.

So a 16(4)A part is a 16 A resistive switch and a 4 A inductive switch. It is not "16 A, with 4 A of inrush headroom". If you put a 0.75 kW motor, a transformer-fed load or an LED driver on it and pull 10 A, you are 2.5x over the inductive rating. The contact set erodes, the arc does not self-extinguish at zero crossing, and somewhere between a few hundred and a few thousand operations the contacts weld closed.

Neither number is an inrush limit. Capacitive and electronic loads pull 20x to 100x rated current for the first few milliseconds after switch-on. A KCD4 that welds on a 60 W LED driver is not a defective switch: it is a switch being asked for a closing current nobody rated it for. Fix it upstream with an NTC, a pre-charge resistor or a relay driven by the rocker, not with a bigger switch.

2. T85 / T105 / T125 is ambient, not surface temperature

The T number is the maximum ambient air temperature around the switch body at which the part still meets its rated current and its temperature-rise limit.

Two consequences that matter in real panels:

  • A T85 switch in a 95 C enclosure is out of spec even though nothing feels hot. Spring temper and contact plating degrade faster than the datasheet's electrical life table assumes, and contact resistance starts to drift upward well before anything visibly fails.
  • Electrical life roughly halves for every 10 C of sustained over-temperature. A "30,000 operations" figure measured at 25 C is not the number you will get at 100 C.

Measure it properly: thermocouple 10 mm from the body, after one hour at rated load, with the enclosure closed. Enclosure air temperature at the top of the box is usually 10-20 C above what the switch actually sees, and measuring that instead is how people end up buying T125 parts they did not need.

3. 30 mΩ contact resistance is a screen, not a thermal number

30 mΩ is a dry-circuit figure: it is measured with a low test current, four-wire, so that probe and lead resistance are excluded.

Do the arithmetic before treating it as a power loss. 16 A through 30 mΩ is 7.7 W in a component the size of a thumbnail. No 30x22 mm rocker survives that. The real thermal acceptance criterion is temperature rise at rated current, not contact resistance, and this is why a switch can pass 30 mΩ on the line and still overheat in service.

Where the number does earn its keep is as a wear screen:

Stage Expected
New part 10-30 mΩ
After 10,000 cycles at rated load 30-50 mΩ
50-100 mΩ worn, plan replacement
>100 mΩ hot joint, do not ship

Use a four-wire milliohm meter. A two-wire multimeter adds 0.2-0.5 Ω of lead and probe resistance and will tell you a good switch is scrap.

4. IPX4 vs IPX6: the X is not a zero

IPX4 is splash from any direction for 10 minutes with an oscillating nozzle. IPX6 is a 12.5 mm nozzle at 100 L/min from 3 m for at least 3 minutes.

IPX6 is not a stronger version of IPX4 in the way people assume: it is a jet test, and a switch can pass 6 while failing 4 if its gasket is designed for pressure but not for pooling. More importantly:

  • X means dust ingress was not tested. IP54 to IP65 is not an upgrade you can assume; it is a different test series.
  • The rating covers the front face, installed in a panel. The rear terminals are not protected by it. Cable side water ingress is a separate problem and usually the one that actually kills the part.
  • The seal is done by the actuator boot and the panel gasket, both of which depend on panel thickness and mounting torque. The same switch is IPX4 in a 2 mm panel and not IPX4 in a 5 mm panel with a deformed gasket.

For rain exposure, IPX4 with a correctly torqued gasket is normally enough. For washdown or hose-directed cleaning you need IPX6 plus a drain path, because a sealed switch in a sealed pocket just fills with condensate.

5. The five questions to ask before you spec

  1. What is the load type: resistive, motor, transformer or capacitive input? Pick the rating that matches.
  2. What is the measured ambient at the switch body with the enclosure closed?
  3. What inrush will the load present for the first 10 ms?
  4. Is water hitting the front face only, or the terminals too?
  5. What electrical life do you need at that load and that temperature, not at 25 C?

Answer those five and the nameplate stops being ambiguous.

I work with a manufacturer of panel switches, fuse holders and IEC 60320 inlets, so treat the numbers above as field notes rather than an independent test report. If you want the same breakdown for more specs (cutout sizes, fuse holder sizes, C14 vs C20, 3-pin pinouts), they are collected on this switch and connector answers page.