arXiv:2611.18428v1 Announce Type: new Abstract: To exploit the grid-support capability of AI data centers (AIDCs), this paper proposes a grid-forming (GFM) control scheme which coordinates the IT loads and energy storage (ES) in the AIDC. First, the framework of a grid-connected AIDC is presented, with the multi-stage power conversion from the grid to the IT loads presented. A dual GFM scheme is then proposed for the back-to-back converters to provide grid support through coordinated power adjustments from IT loads and ES. In addition, an aggregated power response model is established to characterize the IT-load flexibility considering multiple IT servers executing diverse tasks. Time-domain simulations of a 100 MW grid-connected AIDC demonstrate that the proposed control scheme can effectively support the grid.